5 MWh liquid-cooled DC block
20 ft high-cube liquid-cooled BESS container — factory-integrated with partner QA package with manufacturing partner.
Solution / Product Family
5 MWh liquid-cooled BESS container (20 ft DC block) — factory-integrated, full-load tested with our manufacturing partner before shipment.
20 ft high-cube liquid-cooled BESS container — factory-integrated with partner QA package with manufacturing partner.
Air-cooled containerized storage platform for simplified deployment.
Partner certifications, 7.2 MWh test center and capacity figures.
Wide doors and modular cabinets for maintenance and upgrade.
Pull-out liquid-cooling arrangement for service access.
Partner QA package interfaces prepared for site commissioning.
| Battery capacity | 5,015 kWh |
|---|---|
| Dimensions (L × W × H) | 6,058 × 2,438 × 2,896 mm (20 ft HC) |
| Battery system weight | 43,000 kg |
| Energy density (footprint) | 424 kWh/m² (approx. 25% more energy than a conventional 5 MWh block) |
| System efficiency | ≥ 95% |
| Thermal management | Liquid cooling; cell temperature difference ≤ 3 °C |
| Fire safety | Five-layer protection; cell → module → system three-level protection; compartmentalized isolation; 2-hour fire resistance; no thermal-runaway propagation |
| Humidity | 0–100% |
| Altitude | Up to 5,000 m (10% derating above 4,000 m) |
| Compatibility | Drop-in replacement for standard 5 MWh 20 ft blocks; no PCS modification required |
| Standards | UL 9540 compliance path coordinated per market; NFPA 855 / NFPA 70 and export paths discussed per project (documentation on request). Other markets / export: IEC 61000, IEC 62619, IEC 62933, IEC 62477, UN38.3 / UN3536, CE, UKCA, G99, AS 3000 |
| System capacity | 5 MWh |
|---|---|
| Form factor | Standard 20 ft container |
| Total weight | ≤ 44 t (compatible with conventional port and yard handling) |
| Enclosure protection | IP55 (PACK / key components up to IP67) |
| Corrosion protection | C4 |
| Thermal management | Liquid cooling via multi-stage variable-diameter piping or cold plates; module/cell ΔT ≤ 3 °C |
| Fire safety | PACK-to-cabin multi-level aerosol suppression; early thermal-runaway warning; large-scale fire-test documentation shared with qualified buyers on request |
| Controls | Intelligent BMS/EMS, millisecond-level monitoring, cloud connectivity |
| Standards | ISO container standards; UL 9540 compliance path coordinated per market; NFPA 855 / NFPA 70 and export paths discussed per project (documentation on request); UL 1203 where applicable |
Share your SLD / BOD or site constraints — we'll reply with a modular scope and landed-cost path.